Parameterization
D184B140U02 FSM4000
77
Submenu/parameter
Value range
Comment
TOT 1 Channel
Channel setting for totalizer block.
Available only as option TB Flow Value. When setting the
channel, the volume and mass unit is also copied from
UNIT_TOT (e.g.: m
3
/h
→
m
3
).
TB
Flow
Value
TOT
2
Channel
See
TOT
1.
TB
Flow
Value
Software Rev.
Display only
Displays the communication software version.
Communication:
0
FF
Address
0x15
3. FOUNDATION Fieldbus communication.
Displays the address and device ID:
000320 = manuf. code ABB, hex
0017 = Device Type Code FSM4000, hex
_FSM4000_ = Device name
12345 = serial number of device, 5-digit
Dev. ID
0003200017_FSM40
00_12345
Dip Switch
Hardware switch.
IdentNo Selector
There is a 10-position DIP switch in the transmitter. It can
be accessed after opening the cover of the housing. The
switch position is displayed on the device in the data link
submenu. It can also be read via the FF communication in
the transducer block. An open switch is shown as –, a
closed switch as x.
The following switches are assigned:
Switch 1 = Simulate Enable off = Simulation mode disable
on = Simulation Mode enabled.
Switch 2 = Write Protect Off = Simulation Mode disabled
on = Write protect enabled. "Simulation mode enabled"
only allows you to run a simulation, not to actually start
the AI block simulation. Simulation is switched on/off via
the "Simulate" parameter. "Write protect enabled"
prevents overwriting of block parameters. Switches 3-10
have no function.
Profile
0x9700
AI
Error Mask
This menu shows the screen for the error register (TB
Index 95).
Bitstring
0
ON
Line
1
shows the setting of the bit (on/off), which is
indicated by its bitstring number. Line 2 shows the
complete screen in hex characters. Lines 3 and 4 provide
plaintext descriptions of each bit. Select the bits via the
keys Data and Step, and select ENTER to switch the bit
on/off.
See the "Error Register" in the interface description
D184B093U31.
EF0F0000
Error
A
Max. alarm