Commissioning
D184B140U02 FSM4000
57
Seating of DIP switches
G00564
123456789A
On
1
2
Fig. 51: Position of DIP switches
1
Transmitter plug-in module
2
DIP switch
Assigning of DIP switches
DIP switch 1:
Releases the simulation of the AI function blocks.
DIP switch 2:
Hardware write protection for write access via bus (locks all blocks).
DIP switch
1
2
3 ... 10
status
Simulation Mode
Write protect
no function
Off Disabled
Disabled
no
function
On Enabled
Enabled
no
function
Bus address settings
The bus address is automatically allocated at the FF via LAS (link active scheduler). For
address detection, a unique number is used (DEVICE_ID). This number is a combination of
manufacturer ID, device ID and device serial number.
The behavior when switching on the unit corresponds to Draft DIN IEC / 65C / 155 / CDV of
June 1996.
The average current draw of the unit is 10 mA. The voltage on the bus line must lie in the range
of 9 … 32 V DC.
Important
The upper limit of the current is electronically limited. In the event of an error, the integrated
FDE function (Fault Disconnection Electronic) integrated in the device ensures that the current
consumption can rise to a maximum of 13 mA.