Modbus/TCP – Start-up 79
50.03 FBA A comm loss t
out
3.0 s
2)
Defines the fieldbus A
communication break supervision
time.
50.04 FBA A ref1 type
4
= Speed
Selects the fieldbus A reference 1
type and scaling.
51.01 FBA A type
128
= ETHERNET
1)
Displays the type of the fieldbus
adapter module.
51.02 Protocol/Profile
1
= MB/TCP ABB E
Selects the Modbus/TCP protocol
and the ABB Drives - Enhanced
profile.
51.03 Commrate
0
= Auto
2)
Ethernet communication rate is
negotiated automatically by the
device.
51.04 IP configuration
0
= Static IP
2)
Configuration will be obtained
from parameters
05
…
13
.
51.05 IP address 1
192
2)
First part of the IP address
51.06 IP address 2
168
2)
Second part of the IP address
51.07 IP address 3
0
2)
Third part of the IP address
51.08 IP address 4
16
2)
Last part of the IP address
51.09 Subnet CIDR
24
2)
Sets the network mask as
255.255.255.0, allowing access
only to the last subnet.
51.20 Timeout time
10
2)
Sets the communication timeout
as 1 second.
51.21 Timeout mode
2
=
Control RW
2)
The timeout feature monitors the
updating of the Control word and
Reference 1.
52.01 FBA A data in1
01.14
2)
Output power
52.03 FBA a data in3
01.11
2)
DC voltage
53.01 FBA A data out1
22.26
2)
Constant speed 1
53.03 FBA A data out3
22.27
2)
Constant speed 2
51.27 FBA A par refresh
1
= Refresh
Validates the FENA-11/-21
configuration parameter settings.
Drive parameter
Setting for ACS880
drives
Description
Содержание FENA-01
Страница 1: ...Options for ABB drives converters and inverters User s manual FENA 01 11 21 Ethernet adapter module ...
Страница 4: ......
Страница 20: ...20 Safety instructions ...
Страница 32: ...32 Introduction to the manual ...
Страница 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Страница 42: ...42 Mechanical installation ...
Страница 46: ...46 Electrical installation ...
Страница 48: ......
Страница 94: ...94 Modbus TCP Communication profiles ...
Страница 106: ...106 Modbus TCP Communication protocol ...
Страница 112: ...112 Modbus TCP Diagnostics ...
Страница 114: ......
Страница 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Страница 180: ...180 EtherNet IP Communication profiles ...
Страница 246: ......
Страница 297: ...PROFINET IO Start up 297 4 Click and drag the FENA object from the device catalog to the Ethernet 1 PROFINET IO System ...
Страница 304: ...304 PROFINET IO Start up ...