PROFINET IO – Start-up 281
The table below gives the recommended drive parameter settings.
Drive parameter
Setting for
ACS850/ACQ810
drives
Description
50.01 Fba enable
Enable
Enables communication between
the drive and the fieldbus adapter
module.
50.02 Comm loss func
Fault
2)
Enables fieldbus communication
fault monitoring.
50.03 Comm loss t out
3.0 s
2)
Defines the fieldbus communication
break supervision time.
50.04 Fb ref1 modesel
Speed
Selects the fieldbus reference 1
scaling.
51.01 FBA type
Ethernet
1)
Displays the type of the fieldbus
adapter module.
51.02 FBA par2
(PROTOCOL/PROFILE)
10
(= PNIO Pdrive)
Selects the PROFINET IO protocol
and the PROFIdrive profile.
51.03 FBA par3
(COMMRATE)
0
(= Auto
2)
Ethernet communication rate is
negotiated automatically by the
device.
51.04 FBA par4
(IP CONFIGURATION)
0
(= Static IP)
Configuration will be obtained from
parameters
05
…
13
or from the PLC
via the DCP protocol.
52.01 FBA data in1
4
(= SW 16bit)
1)
Status word
52.02 FBA data in2
5
(= Act1 16bit)
Actual value 1 (speed)
52.03 FBA data in3
122
2)
Power
52.05 FBA data in5
107
2)
DC bus voltage
53.01 FBA data out1
1
(= CW 16bit)
1)
Control word
53.02 FBA data out2
2
(= Ref1 16bit)
Reference 1 (speed)
53.03 FBA data out3
2606
2)
Constant speed 1
53.05 FBA data out5
2607
2)
Constant speed 2
51.27 FBA par refresh
Refresh
Validates the FENA-11/-21
configuration parameter settings.
10.01 Ext1 start func
FB
Selects the fieldbus interface as the
source of the start and stop
commands for external control
location 1.
Содержание FENA-01
Страница 1: ...Options for ABB drives converters and inverters User s manual FENA 01 11 21 Ethernet adapter module ...
Страница 4: ......
Страница 20: ...20 Safety instructions ...
Страница 32: ...32 Introduction to the manual ...
Страница 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Страница 42: ...42 Mechanical installation ...
Страница 46: ...46 Electrical installation ...
Страница 48: ......
Страница 94: ...94 Modbus TCP Communication profiles ...
Страница 106: ...106 Modbus TCP Communication protocol ...
Страница 112: ...112 Modbus TCP Diagnostics ...
Страница 114: ......
Страница 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Страница 180: ...180 EtherNet IP Communication profiles ...
Страница 246: ......
Страница 297: ...PROFINET IO Start up 297 4 Click and drag the FENA object from the device catalog to the Ethernet 1 PROFINET IO System ...
Страница 304: ...304 PROFINET IO Start up ...
Страница 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...