Modbus/TCP – Communication protocol 105
(4)00059
DATA IN 3
(4)00060
DATA IN 4
(4)00061
DATA IN 5
(4)00062
DATA IN 6
(4)00063
DATA IN 7
(4)00064
DATA IN 8
(4)00065
DATA IN 9
(4)00066
DATA IN 10
(4)00067
DATA IN 11
(4)00068
DATA IN 12
(4)00101…(4)09999
Drive Parameter Access (16-bit)
Register Address = (4)00000 + 100 × Group +
Index
Example for Drive Parameter 3.18:
(4)00000 + 100 × 3 + 18 = 400318
(4)20000…(4)29999
Drive Parameter Access (32-bit)
(not supported with ACS355):
Register Address = (4)20000 + 200 × Group +
2 × Index
Example for Drive Parameter 1.27:
(4)20000 + 200 × 1 + 2 × 27 = 420254
1)
6-digit register addressing ([4]00001) is used instead of 5-digit register
addressing ([4]0001) to describe register map. See section
Register
addressing
on page
96
for additional information.
2)
Register addresses of the 32-bit parameters cannot be accessed by
using 5-digit register numbers.
Register Address
1), 2)
Register Data (16-bit)
Содержание FENA-01
Страница 1: ...Options for ABB drives converters and inverters User s manual FENA 01 11 21 Ethernet adapter module ...
Страница 4: ......
Страница 20: ...20 Safety instructions ...
Страница 32: ...32 Introduction to the manual ...
Страница 38: ...38 Overview of the Ethernet network and the FENA 01 11 21 module ...
Страница 42: ...42 Mechanical installation ...
Страница 46: ...46 Electrical installation ...
Страница 48: ......
Страница 94: ...94 Modbus TCP Communication profiles ...
Страница 106: ...106 Modbus TCP Communication protocol ...
Страница 112: ...112 Modbus TCP Diagnostics ...
Страница 114: ......
Страница 154: ...154 EtherNet IP Start up 3 In the Select Module window select ETHERNET MODULE ...
Страница 180: ...180 EtherNet IP Communication profiles ...
Страница 246: ......
Страница 297: ...PROFINET IO Start up 297 4 Click and drag the FENA object from the device catalog to the Ethernet 1 PROFINET IO System ...
Страница 304: ...304 PROFINET IO Start up ...
Страница 374: ...374 AppendixA PROFIdriveparametersandI MrecordsofPROFINETIO ...