![ABB ESI-S Скачать руководство пользователя страница 94](http://html1.mh-extra.com/html/abb/esi-s/esi-s_installation-operation-and-maintenance-instructions_3399234094.webp)
94 The ESI-Manager user interface
Manual Energy Storage Inverter ESI-S
−
Deselection of all harmonics
The inverter has to be informed about whether the main window settings or the auxiliary
window settings must be used. This is done by the ‘Activate’ flag
[/Welcome/Settings/Customer set/Activate].
Possible values for this flag are given in
By default the inverter uses the main
inverter settings.
Table 39: Possible settings for the activate field
‘Activate’ field value Description
Main
Main window settings are always used
Auxiliary
Auxiliary window settings are always used
Ext. input
The inverter switches between the main and the auxiliary settings
according to a signal applied to the ESI-Manager’s digital input
(a)
.
Remark:
(a)
Refer to detailed manuals for cabling instructions for this feature. Refer to
Section 7.9.2.4
configuring the digital input for this feature. The external input must be provided to the
ESI-Manager which acts like the “master” unit.
7.9.2.1.1 Setting up the filter mode
For setting up the inverter’s main inverter mode go to [/Welcome/Settings/Customer
set./Main settings/Inverter mode].
For setting up the inverter’s auxiliary inverter mode go to
[/Welcome/Settings/Customer set./Auxiliary settings/Inverter mode].
The inverter can have three types of effect on the network:
−
Inverter the selected harmonics until their magnitudes are close to zero
(Maximum filtering)
−
Inverter the selected harmonics until their magnitudes reach the residual level
permitted by the user (filtering to Curve)
−
Produce or absorb reactive power including load balancing
The user can put the emphasis on one of the above effects by selecting the filtering
mode.
shows the three available modes: