104 The ESI-Manager user interface
Manual Energy Storage Inverter ESI-S
WARNING: If the inverter nominal frequency is changed to the wrong value, the inverter
will refuse to start indicating a frequency error in the event logging window.
−
The active inverter synchronization mode (Synchro Mode): by default single phase
synchronization is used (Single ph.). In exceptional circumstances this may not
be adequate. In that case choose three phase synchronization (Three ph.).
WARNING: This parameter shall only be changed by experienced commissioning
engineers or after advice from the ABB service provider. Using the wrong synchro
mode will lead to inverter malfunctioning.
Remarks:
−
After going through the network characteristics menu, the inverter system will be
automatically reset after which the new values will be taken into account.
−
The inverter needs to be stopped before the network characteristics menu can
be accessed. Attempting to access the menu while the inverter is running will
result in a fault message being displayed.
−
When involuntarily entering the menu, walk through the menu by pressing the
button or following the complete menu. This way the menu can be quit
without modifying any values.
7.9.3.2 Setting up the inverter characteristics
Remarks:
−
The inverter needs to be stopped before the unit ratings menu can be accessed.
Attempting to access the menu while the inverter is running will result in a fault
message being displayed.
−
Pressing the
button in the unit ratings setup menu will result into jumping
to the next step in the menu without the values entered being taken into account.