162 Operating instructions
Manual Energy Storage Inverter ESI-S
WARNING: In case the inverter stops operating due to a fault, very high voltages may
be present on the DC capacitors for a long time. Do not touch any live parts unless you
have ascertained that no dangerous voltage levels exist in the inverter.
−
If the inverter when activating the stop menu displays a message to indicate that
it is remote control mode, the inverter either has to be stopped by remote control
or the remote control mode has to be deactivated. More information about the
remote control functionality is given in
and
−
If the hardware lock and/or the Communication lock has/have been engaged, the
inverter cannot be started nor stopped neither by the local button nor by remote
control. In order to see which lock(s) has/have been engaged push
when
the ‘start/stop’ menu is highlighted. A message will appear to indicate which
lock(s) has/have to be disengaged. If authorized, disengage the relevant lock.
•
The hardware lock can be disengaged by pushing the blue button present
at the bottom rear of the ESI-Manager. More information on the inverter
menu locking facilities is given in
Section 7.6
•
The Communication lock can be engaged in the menu [/Welcome/User
interface/Communication] by ticking the “check box”. More information
on the Communication lock is available in the document
“2GCS212013A0050-RS-485 Installation and Start-up guide”.
The stop sequence conducted when a stop command is given can be derived from the
following flow chart.