Modifications reserved
Page 8/79
2
General information
WARNING!
THIS IS A PRODUCT FOR COMMERCIAL AND INDUSTRIAL APPLICATION
IN THE SECOND ENVIRONMENT AS DEFINED IN IEC/EN 62040-2
CHAPTER 4 – INSTALLATION RESTRICTIONS OR ADDITIONAL
MEASURES MAY BE NEEDED TO PREVENT DISTURBANCES
The UPS must be installed according to the recommendations in this manual. To operate the UPS at
peak efficiency, your installation site should meet the environmental parameters outlined in this
manual. Excessive amounts of dust in the operating environment of the UPS may cause damage or
lead to malfunction. The UPS should always be protected from weather and sunshine. If you intend
to operate the system at an altitude higher than 1000 m, contact your local sales or service office for
important information about high-altitude operation. The operating environment must meet the weight,
airflow, size and clearance requirements specified in the technical datasheet.
Under no circumstances should the UPS be installed in an airtight room, in the presence of flammable
gases, or in an environment exceeding the specification. The basic environmental requirements of the
UPS are:
•
Ambient temperature Range:
0 to +40˚C
(32 – 104˚F)
•
Recommended operating Range:
+20 to +25˚C (68 – 77˚F)
•
Maximum relative Humidity:
95% (non-condensing)
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are
sited in the sides and front of the cabinet, at the bottom, and air outlets are sited in the rear of the
cabinet. You must allow clearance at the back of the cabinet for proper air circulation. Refer to
chapter 5.3: UPS and battery location.
2.1
Declaration of safety conformity and CE marking
The product has the CE marking in compliance with the following European directives:
•
Low Voltage Directive:
2006/95/EC
•
EMC Directive:
2004/108/EC
Declaration of conformity with UPS harmonized standards and directives
EN 62040-1-1 (Safety) and EN 62040-2 (EMC) are available in the annex 1
Product Standards
Standards
Safety Standard:
IEC/EN 62040-1
IEC/EN 60950-1
Electromagnetic Compatibility
Standard (EMC):
IEC/EN 62040-2
Emission cat. C3
Immunity cat. C3
IEC/EN 61000-6-2
IEC/EN 61000-6-4
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
Performance Standard:
IEC/EN 62040-3
Содержание DPA UPScale ST120
Страница 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Страница 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Страница 78: ......
Страница 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Страница 104: ......
Страница 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...