Modifications reserved
Page 26/79
5
Installation
5.1
Environmental condition
The UPS is designed for indoor location, in a restricted access location only and should be located as
follows:
5.1.1
Climatic conditions
Ambient temperature
º
C
0 to +40
Relative humidity
%
95
Conditions of condensation
no
Presence of wind-driven rain,
snow, hail, etc
no
Conditions of water from sources
other than rain
no
Icing conditions
no
The climate control system could be periodically switched on or off, but extremely high or low
temperatures should be avoided.
5.1.2
Biological conditions
Flora (presence of mould, fungus)
no
Fauna (presence of rodents and other animals)
no
The location should not have a particular risk of biological attacks.
5.1.3
Mechanical active substance
The UPS shall not be placed in proximity to a source of sand or dust.
5.1.4
Chemical active substance
The location can have a normal level of contaminants experienced in urban areas over the whole area.
5.1.5
Mechanical conditions
The UPS shall be placed in a location with no significant exposure to vibration and shock.
5.2
Enviromental condition for UPS with inside battery modules
As the battery life depends on the ambient temperature, for the UPS with internal battery modules it is
recommended to have a location with a climate-controlled system to maintain the conditions as
follows:
5.2.1
Climatic conditions
Ambient temperature
º
C
20
Содержание DPA UPScale ST120
Страница 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Страница 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Страница 78: ......
Страница 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Страница 104: ......
Страница 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...