Modifications reserved
Page 8/26
6
Battery characteristics
Module type
UPScale M10
UPScale M20
Battery type
-
Maintenance-free VRLA or NiCd
No. VRLA 12 V battery blocks
@ max. rated output power
-
30
2)
- 50
40
2)
- 50
Allowed no. of 1.2 V NiCd cells
@ max. rated output power
-
300
2)
- 500
400
2)
- 500
Floating voltage
VDC
VRLA: 2.25 V/cell - NiCd: 1.4 V/cell
End of discharge voltage
VDC
VRLA: 1.65 V/cell - NiCd: 1.05 V/cell
Maximum charging current
per module
A
4 (6 A charger is optional)
Battery charging curve
-
Ripple-free; IU (DIN 41773)
Temperature compensation
-
Standard (temp. sensor optional)
Battery test
-
Automatic and periodically (adjustable)
2)
Min battery block range allowed under following conditions:
Module type
UPScale M10
UPScale M20
No. VRLA 12 V battery blocks
-
30-32
34-50
40-46
48-50
Max power
kW
6
10
10
16
20
20
Max autonomy
min
any
5
any
any
5