Modifications reserved
Page 20/26
15
Installation planning – UPS positioning
The minimum clearances as described below that are needed to allow proper airflow to the UPS
system, and to allow proper service and maintenance, should be respected.
DPA UPScale S2 cabinets
ST40, ST60, ST80, ST120
ST200
UPS + battery
cabinets in row.
A
Back clearance for ventilation
(forced air outlet)
200 mm
300 mm
B
Front clearance needed to
allow correct door opening
1000 mm
C
Maximum door opening
angle
115°
D
Top clearance
(Top clearance is only needed if
there is no side clearance)
400 mm
Содержание DPA UPScale ST120