96
DPA 2 50 S 4 50 - 2 50 K W
O P ER AT I N G M A N UA L
5. Verify that the operating parameters are cor-
rectly set in the module.
• Battery type, the number of blocks/cells,
autonomy time, set as “Common” or “Sepa-
rate” etc.
• Setting for output voltage and frequency.
• Module and frame identification numbers.
6. Load ON the module by means of the ON/
OFF button present on its control panels (Al-
ways confirm with “ENTER” when required)
7. Check if the starting sequence is correctly ex-
ecuted, with the module running according
to the parallel system operation mode at the
end (INVERTER or STATIC BYPASS mode).
8. Turn to ON position (close) the relative mod-
ule battery breakers present on the frames.
Wait until the BATTERY LED turns green (ap-
prox. 1 or 2 minutes), this means that the bat-
teries are connected and are ok.
The module is now protecting the load in par-
allel with all other modules present in the
system.
INVERTER MODE
LED indicators status on all operating modules
Display on all operating modules
LED INDICATION
COLOR
SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier
Green
Bypass
Green
Load
Green
Battery
Green
BYPASS MODE (ECO MODE)
LED indicators status on all operating modules
Display on all operating modules
LED INDICATION
COLOR
SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier
Green
Bypass
Green
Load
Yellow
Battery
Green
The load is now protected by the DPA 250 S4 UPS.