Rectifier Float Set
-
point:
The voltage at which the plant will float charge the battery strings.
Rectifier Boost Set
-
point:
The voltage at which the plant will boost charge the battery strings.
Redundancy Monitor Enable:
Activates the Redundancy Loss alarm feature.
Rectifier Management
Related Commands
obj,attr
description
sta
cha
ope
type
range of values
gm1,fsp
Rectifier float set
-
point
x
x
number
51
-
56.5,
54.5 V
gm1,bsp
Rectifier boost set
-
point
x
x
number
54
-
56.5,
55.2 V
gm1,rme
Redundancy monitor enable
x
x
number
0: disable
, 1: enable
Rectifiers
Related Commands
obj,attr
description
sta
cha
ope
type
range of values
gsr,stt
Individual rectifier state
r
x
text
“
ON
”, “
OFF
”, “
STANDBY
”,
“
MISSING
”
Only
“
ON
”
and
“
STANDBY
”
can be used
with ope.
gsr,adc
Individual rectifier current
x
number
ddd
Individual Rectifier State:
When requested, shows the state of the individual rectifiers. Note that the
rectifier numbering starts from the left
-
most position of the master shelf (shelf number 1.)
When obtaining individual rectifier status information, the following information may be transmitted:
•
ON:
Rectifier operating normally. User may use ope to turn ON a rectifier in standby.
•
OFF:
Rectifier has been shutdown due to hardware failure.
•
STANDBY:
User has inhibited the rectifier's output voltage. User may use ope to place a rectifier into a standby
condition.
•
MISSING:
An acknowledged rectifier has been removed.
•
VACANT:
Rectifier has not been installed in that position.
Rectifiers may also be put in standby; however, the ability to place rectifiers in standby requires some
backup plan to take the rectifier out of standby automatically under a low voltage condition. The
battery on discharge (BOD) threshold is used as a rectifier
-
on voltage threshold. In other words, when
the plant voltage dips below the BOD threshold, the controller turns on all rectifiers that are in standby.
Individual Rectifier Current:
When requested, shows the current output from an individual rectifier.
Содержание CPS6000
Страница 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 36: ...Page 36 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 98: ...Page 98 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 105: ...Page 105 Copyright 2021 ABB All rights reserved Figure 7 5 Configuration Menu part 1 Configuration Menu ...
Страница 106: ...Page 106 Copyright 2021 ABB All rights reserved Figure 7 6 Configuration Menu part 2 Configuration Menu continued ...
Страница 124: ...Page 124 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 146: ...Page 146 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 152: ...Page 152 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 174: ...Page 174 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 188: ...Page 188 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 196: ...Page 196 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 198: ...Page 198 Copyright 2021 ABB All rights reserved This page intentionally left blank ...