Figure 5
-
21: GMT Fuse Connections, Single
-
Slot Distribution Module
Terminate Load Connections
-
GMT Fuses
Single
-
Slot Distribution
When using 20 A fuses adjacent fuse positions must be left open. No more than 80A may be carried
through the 10 fuse positions, or 40A per half
-
section. Up to 14 AWG wire can be used to connect loads
to each of the fuse positions. See Figure 5
-
21 for fuse position and terminal block designations.
Double
-
Slot Distribution
The 16 GMT fuse position terminal blocks will accommodate 10 AWG wire. Each fuse board (A and B) has
8 GMT positions and is sized to handle up to 80A of total current and can support up to four 20 amp
fuses if spaced properly. If 20A fuses are used, then adjacent fuse positions must be left empty. See
Figure 5
-
22 for fuse position and terminal block designations.
Step
Action
1.
Strip 0.24 inches (0.6cm) of insulation from the wire.
2.
Insert the stripped wire through the side of the shelf and into the screw terminal. Torque to 4.5 in. lbs
(0.5 Nm). See Figure 5
-
21 for Single
-
Slot, and Figure 5
-
22 for Double
-
Slot Distribution Modules.
Load
Return
Terminal
5 Primary / Secondary
GMT Fuse Positions
GMT Fuse Load
Power And Return
Terminal Blocks
5 Primary GMT
Fuse Position
Half–
Section
Half–
Section
GMT Fuse Terminal Blocks
GMT Fuse Positions
Load
Power
Terminal
Содержание CPS6000
Страница 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 36: ...Page 36 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 98: ...Page 98 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 105: ...Page 105 Copyright 2021 ABB All rights reserved Figure 7 5 Configuration Menu part 1 Configuration Menu ...
Страница 106: ...Page 106 Copyright 2021 ABB All rights reserved Figure 7 6 Configuration Menu part 2 Configuration Menu continued ...
Страница 124: ...Page 124 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 146: ...Page 146 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 152: ...Page 152 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 174: ...Page 174 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 188: ...Page 188 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 196: ...Page 196 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 198: ...Page 198 Copyright 2021 ABB All rights reserved This page intentionally left blank ...