Page 134
© Copyright 2021 ABB. All rights reserved.
•
Excessive Temperature Reduced Output:
Ringer output is reduced due to high Ringer component temperature.
Recovery is automatic when component temperatures return to safe values.
Excessive Output Load: Ringer output load exceeds 100VA.
Reduced Output: Ringer provides limited ringing output at 100VA by reducing Vac as low as 50% of Vac set point.
Hiccup: If Ringer output is overloaded to Vac less than approximately 50% of the Vac set point, the Ringer enters
the hiccup mode.
Recovery is automatic when the external fault is removed.
In this mode, the Ringer shuts
-
down and restarts briefly at intervals of approximately 2 minutes to test for the
presence of the external fault.
Restart will cause restart immediately.
•
Internal Fault: Ringer output is disabled (shutdown) due to excessive temperature or Ringer failure.
Recovery from Internal Fault
Excessive Temperature recovery is automatic when the temperature returns to a safe value.
Ringer Failure recovery is manual, requiring one of the following:
•
Removal of dc input power (remove and re
-
install Ringer in Ringer Chassis)
•
Restart command from Controller (from front panel menu or remote)
•
Ringer Failure is usually permanent and will reoccur upon completion or the recovery attempt.
Содержание CPS6000
Страница 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 36: ...Page 36 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 98: ...Page 98 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 105: ...Page 105 Copyright 2021 ABB All rights reserved Figure 7 5 Configuration Menu part 1 Configuration Menu ...
Страница 106: ...Page 106 Copyright 2021 ABB All rights reserved Figure 7 6 Configuration Menu part 2 Configuration Menu continued ...
Страница 124: ...Page 124 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 146: ...Page 146 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 152: ...Page 152 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 174: ...Page 174 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 188: ...Page 188 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 196: ...Page 196 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 198: ...Page 198 Copyright 2021 ABB All rights reserved This page intentionally left blank ...