Product Description
CPS6000 System Overview
CPS6000 power systems are comprised of shelves, rectifiers, ringer chassis, ringers, and distribution
modules. Several types of distribution modules are available. The Bulk Output Module provides
connection to an external distribution without consuming a shelf power slot.
The CPS6000 is available as single
-
shelf systems and multiple
-
shelf systems with both 19
-
inch and
23
-
inch shelves.
Single Shelf Systems
•
With Distribution Module: all components contained in single shelf.
•
With Bulk Output Module: uses external distribution, accommodates all other components within the shelf.
Multi
-
Shelf Systems
•
With Bulk Output Module: uses external distribution, accommodates all other components within the shelves.
AC power is supplied to the rectifiers which produce regulated
-
48V dc output voltage. This voltage is
used to power all other system components including ringers, the system controller and the LVD
boards. Batteries are connected to distribution, internal or external. Some Distribution Modules
provide battery circuit breakers. Single
-
Slot and Double
-
Slot Distribution Module options include
GMT
-
style fuses and bullet
-
style circuit breakers.
Ringer Chassis may be installed in Power Slots. Each Ringer Chassis supports one ringing output in
either non
-
redundant (simplex) or 1 + 1 redundant (duplex) operation. Ringer distribution is direct from
the Ringer Chassis. Ringers power ringing signaling outputs and are powered by
-
48V
dc
.
The batteries are monitored by the system controller to ensure their peak performance and longevity
against thermal issues. They are monitored via the Voltage/Thermal Probes (VT
-
Probes), which are
connected from the Distribution Module to the battery.
The Remote Voltage Monitor (RVM) module may be used with the VT
-
Probes in making voltage
measurements for battery string
-
voltage imbalance detection. Additional VT
-
Probes may used by
connecting them in a daisy
-
chain fashion.
The system controller monitors all system parameters and performs battery management functions. It
communicates with all devices using the RS
-
485 bus. The RVM and VT
-
Probe communicate with the
controller using the 1
-
Wire® from Maxim Integrated Products, Inc.
The LVBD contactor is used to connect the battery strings to the main power bus. Under ac fail
conditions, the battery current will be flowing through the contactor to the output distribution in
supporting the load. To prevent deep discharge of batteries, the CPS6000 can disconnect the batteries
from the load by opening the LVBD contactor.
CPS6000 also offers an optional low voltage load disconnect (LVLD) contactor. Non
-
critical loads and
loads sensitive to low voltages can be connected to the system via the LVLD in the Distribution Module.
CPS6000 disconnects these loads at a set threshold during a battery discharge. This reduces drain on
the batteries and extends reserve time available for critical loads.
With the Bulk Output Module, a supplementary shelf may be paralleled to the primary shelf to create a
larger plant. Only the primary shelf would contain the system controller. The supplementary shelf only
requires signal connections to the primary shelf, and power connections to an external distribution
panel. The controller can monitor for open protectors, current from a battery shunt, and monitor and
control a low voltage disconnect contactor via the Remote Distribution Module (RDM).
Содержание CPS6000
Страница 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 36: ...Page 36 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 98: ...Page 98 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 105: ...Page 105 Copyright 2021 ABB All rights reserved Figure 7 5 Configuration Menu part 1 Configuration Menu ...
Страница 106: ...Page 106 Copyright 2021 ABB All rights reserved Figure 7 6 Configuration Menu part 2 Configuration Menu continued ...
Страница 124: ...Page 124 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 146: ...Page 146 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 152: ...Page 152 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 174: ...Page 174 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 188: ...Page 188 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 196: ...Page 196 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Страница 198: ...Page 198 Copyright 2021 ABB All rights reserved This page intentionally left blank ...