7.5 Totalizer
Two 9-digit totalizers are provided. These can be configured independently to totalize any analog or digital
signal. Four modes of operation are provided.
Where possible, the count rate is calculated automatically according to source units, totalizer units and
engineering range.
Totalizer 1 (2)
Mode
Off
Totalizer disabled.
Analog
Totalization of any analog signal.
Digital
Counting of low / high transitions of any digital signal (for example, digital input or alarm) minimum
pulse duration >125 ms.
Frequency
Totalization of a frequency input on Analog input 1.
Pulse
Totalization of a pulse input on Analog input 1.
S
ource
The input to be totalized. The inputs available for selection are dependent on the
Mode
selected.
Not displayed for frequency and pulse inputs – see Appendix A, page 94 for description of
sources.
Menu
Totalizer