![ABB ControlMaster CM15 Скачать руководство пользователя страница 88](http://html.mh-extra.com/html/abb/controlmaster-cm15/controlmaster-cm15_user-manual_2340088.webp)
ControlMaster CM15 and CMF160
Universal process indicator
1
/
8
DIN
10 Specification
86
IM/CM/I–EN Rev. P
10 Specification
Operation
Display
Color,
1
/
4
VGA TFT, liquid crystal display (LCD) with built-in backlight
Language
English, German, French, Italian and Spanish
Operator keypad
CM15: 4 tactile membrane keys
CMF160: 6 tactile membrane keys
Security
Password protection
Basic / Advanced – user-assigned (not factory-set)
Standard functions
Templates
Process alarms
Number
8
Types
High / Low process and High / Low latch
Source
Fully configurable
(for example – PV, Analog input, Math block inbuilt)
Hysteresis
Level and time
Alarm enable
Enable / Disable individual alarms via a digital signal
Acknowledgement
Via front panel keys or digital signals
Real-time alarms *
*Functionality level 'Standard' and above only
Base
Single PV indication
Single PV indi totalizer
Counter
Single PV indi level
Dual
Dual PV indication
Dual PV indi totalizer
Dual counter
Dual PV indi level
Number
2
Programmable Time
Day
Duration