ControlMaster CM15 and CMF160
Universal process indicator
1
/
8
DIN
4 Installation
IM/CM/I–EN Rev. P
21
4.5.1 CM15 Indicator
Fig. 4.13 ControlMaster CM15 Electrical Connections
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
+
+
+
+
+
19
20
21
22
23
24
25
26
27
28
29
30
25
26
Option Board 1
Co
mm
s*
Tx
PSU
Analog / Digital
Output 1****
Analog Input 1
Analog Input 2
Relay Output 1
Neutral
Line***
100 to
240 V AC
10 W
10 to
36 V DC
NC
C
NO
Analog Output 2
Digital Input / Output 1
Digital Input / Output 2
Digital Input / Output –
Relay Output 2
Relay Output 3
Relay
Output 4
Digital External
**
C
**
C
**
C
Standard Connections
Rear View
Rear View
*
**
***
****
Refer to rear panel for MODBUS connections
N/O or N/C contact selection made via internal jumper links – see page 17
200 mA Type T fuse (mains AC) or 2 A Type T fuse (120 V DC max.) and external
isolating switch. For UL-marked indicators the fuse must be UL recognized
Provides 24 V digital output (o and – connections)
Option Board 1a
**
C
Relay Output 2