7.6 Functions
Contains parameters for setting up the math block(s), logic equations and timer functions within the
indicator.
Logic Equations
Up to 8 logic equations can be configured. Each can combine up to 8 operands (digital signals)
with 7 operators. The elements of each equation are calculated sequentially. Operand 1, Operator
1 and Operand 2 are evaluated first. The result is combined with Operator 2 and Operand 3. This
result is then combined with the next operator and operand and so on to the end of the equation.
Note
. If any of the operand sources are invalid (for example, an alarm that is not configured), the
logic equation output state is zero and invalid.
*2 Logic equations are required to perform an exclusive OR of 3 inputs
Menu
Functions
OR, AND
NOR, NAND
EXOR, END
OR, AND
NOR, NAND
EXOR, END
OR, AND
NOR, NAND
EXOR, END
OR, AND
NOR, NAND
EXOR, END
Operand 1
Operand 2
Operand 3
Operand 4
Operand 5
Operator 1
Operator 2
Operator 3
Operator 4
Key:
OR*
AND
NOR
NAND
EXOR
END
Output is 1 if either or both inputs are 1; output is 0 if both
inputs are 0
Output is 1 if both inputs are 1; output is 0 if either input is 0
Output is 0 if either or both inputs are 1; output is 1 if both
inputs are 0
Output is 0 if both inputs are 1; output is 1 if either input is 0
Output is 0 if both inputs are 0 or both inputs are 1; output
is 1 if one input is 1 and the other is 0
Terminates the equation.