ControlMaster CM15 and CMF160
Universal process indicator
1
/
8
DIN
1 Safety
IM/CM/I–EN Rev. P
5
1.4 UL Class I, Division 2 (CMF160 only – when ordered)
This equipment is suitable for use in Class I, Division 2, groups A, B, C, and D hazardous locations or non-hazardous
locations only.
WARNING!
Do not open equipment in an explosive atmosphere.
This equipment must be installed in accordance with the pertinent clauses of the National Electrical Code and/or
Canadian Electrical Code for hazardous locations.
The terminal cover retaining screw must be tightened to a torque of 50 cN.m.
WARNING!
Explosion hazard! Substitution of components may impair suitability for class I, division 2
1.5 UL Class I, Division 2 (CMF160 si commandé)
Cet équipement est adapté uniquement à une utilisation en zones dangereuses de classe I, division 2, groupes A, B,
C et D ou non dangereuses.
ATTENTION !
Ne pas ouvrir l'équipement dans une atmosphère explosive.
Cet équipement doit être installé conformément aux clauses du Code électrique national pour les Etats-Unis ou au
Code électrique canadien pour le Canada relatives aux zones dangereuses.
La vis de fixation du couvercle de protection de borne doit être serrée à un couple de 50 cN.m.
ATTENTION !
Risque d'explosion ! Le remplacement de certains composants peut compromettre la conformité à la
classe I, division 2.