Cyclic loads
If the load cycle is shorter than 10 seconds, the thermal time constant of the heatsink can be ignored,
and the following simple procedure can be applied to find out whether the drive can handle the cycle.
1. Determine the rms value (
I
2rms
) of the output current over the whole load cycle.
2. Determine the maximum instantaneous rms value (
I
2peak
) of the output current during the load cycle.
3. Determine the point (
I
2rms
,
I
2peak
) on the graph below.
If the point falls within the region bordered by a solid line, the load cycle is safe. For
I
2contxk
and
I
2max
,
use the ratings stated for the drive type and switching frequency used.
If the point falls within the shaded area, a more detailed study is required.
The above procedure can also be applied to longer load cycles by dividing the cycle into subcycles no
longer than 10 seconds. If any of the subcycles fail the test, a more detailed study is required.
The DriveSize dimensioning tool available from ABB is recommended for more detailed dimensioning.
I
2rms
I
2peak
I
2contxk
0.75×
I
2contxk
I
2max
I
2contxk
Содержание ACSM1-04 Series
Страница 1: ...ACSM1 Hardware Manual ACSM1 04 Drive Modules 55 to 110 kW ...
Страница 2: ......
Страница 4: ......
Страница 18: ...About this manual 18 ...
Страница 22: ...The ACSM1 04 22 ...
Страница 64: ...Electrical installation 64 ...
Страница 70: ...Maintenance 70 ...
Страница 82: ...Technical data 82 ...
Страница 88: ...Dimension drawings 88 Drive module ...
Страница 89: ...Dimension drawings 89 Drive module continued from previous page ...
Страница 91: ......