Technical data
72
Derating
The continuous output currents stated above must be derated if any of the following conditions apply:
• the ambient temperature e40 °C (+104°F)
• the AC supply voltage is higher than 400 V
• the drive is installed higher than 1000 m above sea level.
Note:
The final derating factor is a multiplication of all applicable derating factors.
Ambient temperature derating
In the temperature range +40…55 °C (+104…131 °F), the output current is derated linearly as follows:
AC supply voltage derating
With AC supply voltages above 400 V AC, the output current is derated linearly as follows:
Altitude derating
At altitudes from 1000 to 4000 m (3300 to 13123 ft) above sea level, the derating is 1% for every 100 m
(328 ft). For a more accurate derating, use the DriveSize PC tool.
Note:
If the installation site is higher than 2000 m (6600 ft) above sea level, connection of the drive to
an ungrounded (IT) or corner-grounded delta network is not allowed.
Ambient temperature
Derating factor
1.00
0.70
+40 °C
+55 °C
+104 °F
+131 °F
AC supply voltage [V]
Derating factor
1.00
0.86
400
480