Electrical installation
61
Drive-to-drive link (X5)
The drive-to-drive link is a daisy-chained RS-485 transmission line that allows basic
master/follower communication with one master drive and multiple followers.
Termination activation jumper J3 (see section
block must be set to the ON position on the drives at the ends of the drive-to-drive
link. On intermediate drives, the jumper must be set to the OFF position.
Shielded twisted-pair cable (~100 ohm, e.g. PROFIBUS-compatible cable) must be
used for the wiring. For best immunity, high quality cable is recommended. The cable
should be kept as short as possible; the maximum length of the link is 50 metres
(164 ft). Unnecessary loops and running the cable near power cables (such as motor
cables) must be avoided. The cable shields are to be grounded to the control cable
clamp plate on the drive as shown on page
.
The following diagram shows the wiring of the drive-to-drive link.
Safe Torque Off (X6)
For the drive to start, both connections (OUT1 to IN1, and OUT2 to IN2) must be
closed. By default, the terminal block has jumpers to close the circuit. Remove the
jumpers before connecting an external Safe Torque Off circuitry to the drive. See
page
X5:D2D
...
1
T
J3
Termination
ON
JCU
Drive 1
B
2
A
3
BG
N
D
X5:D2D
1
J3
Termination
OFF
JCU
Drive 2
B
2
A
3
BG
N
D
T
X5:D2D
1
T
J3
Termination
ON
JCU
Drive n
B
2
A
3
BG
N
D
Содержание ACSM1-04 Series
Страница 1: ...ACSM1 Hardware Manual ACSM1 04 Drive Modules 55 to 110 kW ...
Страница 2: ......
Страница 4: ......
Страница 18: ...About this manual 18 ...
Страница 22: ...The ACSM1 04 22 ...
Страница 64: ...Electrical installation 64 ...
Страница 70: ...Maintenance 70 ...
Страница 82: ...Technical data 82 ...
Страница 88: ...Dimension drawings 88 Drive module ...
Страница 89: ...Dimension drawings 89 Drive module continued from previous page ...
Страница 91: ......