Mechanical installation
30
Before installation
Check the installation site according to the requirements below. Refer to
for frame details.
Requirements for the installation site
See
for the allowed operation conditions of the drive.
The ACSM1-04 is to be mounted in an upright position. The wall the drive is to be
mounted on must be as even as possible, of non-flammable material and strong
enough to carry the weight of the drive. The floor/material below the drive must be
non-flammable.
Connection to an IT (ungrounded) or a corner-grounded power system
The internal EMC filter must be disconnected if the drive is to be supplied from a
corner-grounded power system or an IT power system [an ungrounded power
system or a high resistance-grounded (over 30 ohms) power system]. As the
procedure involves the removal of drive module covers, it is convenient to perform it
before the drive is installed.
See page
for directions.
Installation procedure
Direct wall mounting
1. Mark the locations for the four holes. The mounting points are shown in
2. Fix the screws or bolts to the marked locations.
3. Position the drive onto the screws on the wall.
Note:
Only lift the drive by its lifting
holes.
4. Tighten the screws.
Содержание ACSM1-04 Series
Страница 1: ...ACSM1 Hardware Manual ACSM1 04 Drive Modules 55 to 110 kW ...
Страница 2: ......
Страница 4: ......
Страница 18: ...About this manual 18 ...
Страница 22: ...The ACSM1 04 22 ...
Страница 64: ...Electrical installation 64 ...
Страница 70: ...Maintenance 70 ...
Страница 82: ...Technical data 82 ...
Страница 88: ...Dimension drawings 88 Drive module ...
Страница 89: ...Dimension drawings 89 Drive module continued from previous page ...
Страница 91: ......