Electrical installation
62
Control cable grounding
The shields of all control cables connected to the JCU Control Unit must be
grounded at the control cable clamp plate. Use three M4 screws to fasten the plate
as shown below left. The plate can be fitted either at the top or bottom of the JCU.
The shields should be continuous as close to the terminals of the JCU as possible.
Only remove the outer jacket of the cable at the cable clamp so that the clamp
presses on the bare shield. At the terminal block, use shrink tubing or insulating tape
to contain any stray strands. The shield (especially in case of multiple shields) can
also be terminated with a lug and fastened with a screw at the clamp plate. Leave
the other end of the shield unconnected or ground it indirectly via a few nanofarads
high-frequency capacitor (e.g. 3.3 nF / 630 V). The shield can also be grounded
directly at both ends if they are
in the same ground line
with no significant voltage
drop between the end points.
Keep any signal wire pairs twisted as close to the terminals as possible. Twisting the
wire with its return wire reduces disturbances caused by inductive coupling.
Mounting the clamp plate
Use shrink tubing or
tape to contain
strands
0.7 N·m
(6.2 lbf·in)
Remove outer jacket of
cable at clamp to
expose cable shield.
Tighten to 1.5 N·m
(13 lbf·in)
Содержание ACSM1-04 Series
Страница 1: ...ACSM1 Hardware Manual ACSM1 04 Drive Modules 55 to 110 kW ...
Страница 2: ......
Страница 4: ......
Страница 18: ...About this manual 18 ...
Страница 22: ...The ACSM1 04 22 ...
Страница 64: ...Electrical installation 64 ...
Страница 70: ...Maintenance 70 ...
Страница 82: ...Technical data 82 ...
Страница 88: ...Dimension drawings 88 Drive module ...
Страница 89: ...Dimension drawings 89 Drive module continued from previous page ...
Страница 91: ......