Derating
The load capacity (current and power) decreases if the installation site altitude exceeds
1000 meters (3281 ft), or if the ambient temperature exceeds 50 °C (+122 °F).
Ambient temperature derating
With ambient temperatures below +50 °C (+122 °F), no derating is needed. In the temperature
range +50 °C (+122 °F) … +60 °C (+140 °F), the rated output current is decreased by 2.5%
for every additional 1 °C (1.8 °F) compared to +45 °C (+113 °F). The output current is
calculated by multiplying the current given in the rating table by the derating factor.
Example If the ambient temperature is 55 °C (+131 °F), the derating factor is
100% - 2.5 %/°C · 10 °C = 75% or 0.75. The output current is then 0.75 ·
I
gen
.
Altitude derating
At altitudes from 1000…2000 m (3281…6562 ft) above sea level, the derating is 0.5% for
every 100 m (328 ft). Derating is allowed only on maximum continuous current for grid and
generator. If the installation site is located higher than 2000 m (6562 ft) above sea level,
contact your local ABB representative.
Alternatively the derating can be handled with cooling liquid temperature derating. 1 °C for
every 100 m. This means that in eg, 2000 m installation, the maximum liquid temperature
is 40 °C (instead of 50 °C) instead of 5% current derating.
Type equivalence table
Basic module type (R9iLC)
Construction type
Converter type
ACS880-87LC-
Grid-side converter
Generator-side converter
ACS880-104LC-… (+E205)
ACS880-104LC-… (+E205)
Generator-side converter
m Grid-side con-
verter LCL
U
N
= 690 V
0860A-7
0900A-7+D150
2×(4×R9iLC + 4×R9iLC +
1×LCL)
3200A/3200A-7
3AXD10000011539
Fuses
■
Main circuit AC fuses
AC fuses
Converter type
ACS880-87LC-
Qty
I
N
A rms
Type
U
N
= 690 V
2×12
1250
Bussmann 170M6416
3200A/3200A-7
3AXD10000011539
92 Technical data
Содержание ACS880-87LC-3200A
Страница 1: ... ABB WIND TURBINE CONVERTERS ACS880 87LC 3200A 3200A 7 wind turbine converters Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...10 ...
Страница 18: ...5 1 3 4 6 8 7 2 18 Safety instructions ...
Страница 48: ...48 ...
Страница 68: ...68 ...
Страница 75: ...b 3 a 2 6 c 4 Air flow direction is towards the converter module Maintenance 75 ...
Страница 85: ...14 Open the installation stand optional and place it in front of the module 14 Maintenance 85 ...
Страница 108: ...108 ...
Страница 112: ...Description CAN bus connection XCAN XCAN 112 BCU x5 control unit ...
Страница 116: ...116 Dimension drawings ...
Страница 117: ...Dimension drawings 117 ...
Страница 118: ...118 Dimension drawings ...
Страница 130: ...130 ...