■
Generator stator and generator cable
Check the insulation of the generator stator and cable as follows:
• Check that all cables are disconnected from the converter output terminals U2, V2 and
W2.
• Measure the insulation resistance between each phase conductor and the protective
ground conductor using a measuring voltage of 1000 V DC. The insulation resistance of
an ABB generator must exceed 100 Mohm (reference value at 25 °C (77 °F)). For the
insulation resistance of other generators, please consult the manufacturer’s instructions.
•
Note:
Make sure that there is no condensed moisture inside the generator casing. If you
suspect that there is moisture, dry the generator before measurement.
•
Note:
When using permanent magnet generator, it must be stable at the time of the
measurement.
ohm
G
3~
U1
V1
W1 PE
Connecting the grid cables
■
Connection diagram
U<
PE
L1
L2
L3
PE
62 Electrical installation
Содержание ACS880-87LC-3200A
Страница 1: ... ABB WIND TURBINE CONVERTERS ACS880 87LC 3200A 3200A 7 wind turbine converters Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...10 ...
Страница 18: ...5 1 3 4 6 8 7 2 18 Safety instructions ...
Страница 48: ...48 ...
Страница 68: ...68 ...
Страница 75: ...b 3 a 2 6 c 4 Air flow direction is towards the converter module Maintenance 75 ...
Страница 85: ...14 Open the installation stand optional and place it in front of the module 14 Maintenance 85 ...
Страница 108: ...108 ...
Страница 112: ...Description CAN bus connection XCAN XCAN 112 BCU x5 control unit ...
Страница 116: ...116 Dimension drawings ...
Страница 117: ...Dimension drawings 117 ...
Страница 118: ...118 Dimension drawings ...
Страница 130: ...130 ...