Routing the cables
Route the generator cable away from other cable routes. It is recommended that the generator
cable, grid cable and control cables are installed on separate trays. Avoid long parallel runs
of generator cables with other cables in order to decrease electromagnetic interference
caused by the rapid changes in the converter output voltage.
Where control cables must cross power cables make sure they are arranged at an angle
as near to 90° as possible. Do not run extra cables through the converter.
The cable trays must have good electrical bonding to each other and to the grounding
electrodes. You can use aluminum tray systems to improve local equalizing of potential.
A diagram of the cable routing is below.
90°
min. 500 mm (20 in)
min. 200 mm (8 in)
min. 300 mm (12 in)
1
2
3
4
4
5
Converter
1
Grid cable
2
Control cables
3
Generator cable
4
Power cable
5
Planning the electrical installation 57
Содержание ACS880-87LC-3200A
Страница 1: ... ABB WIND TURBINE CONVERTERS ACS880 87LC 3200A 3200A 7 wind turbine converters Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...10 ...
Страница 18: ...5 1 3 4 6 8 7 2 18 Safety instructions ...
Страница 48: ...48 ...
Страница 68: ...68 ...
Страница 75: ...b 3 a 2 6 c 4 Air flow direction is towards the converter module Maintenance 75 ...
Страница 85: ...14 Open the installation stand optional and place it in front of the module 14 Maintenance 85 ...
Страница 108: ...108 ...
Страница 112: ...Description CAN bus connection XCAN XCAN 112 BCU x5 control unit ...
Страница 116: ...116 Dimension drawings ...
Страница 117: ...Dimension drawings 117 ...
Страница 118: ...118 Dimension drawings ...
Страница 130: ...130 ...