Use
1. Open the activation switch, or activate the safety functionality that is wired to the STO
connection.
2. The STO inputs on the drive control unit de-energize, and the control unit cuts off the
control voltage from the output IGBTs.
3. The control program generates an indication as defined by parameter
31.22
(see the
firmware manual of the drive).
4. The motor coasts to a stop (if running). The drive will not restart while the activation
switch or safety relay contacts are open.
5. Deactivate the STO by closing the activation switch, or resetting the safety functionality
that is wired to the STO connection.
6. Reset any faults before restarting.
WARNING!
The Safe torque off function does not disconnect the voltage of the main and
auxiliary circuits from the drive. Therefore maintenance work on electrical parts of
the drive or the motor can only be carried out after isolating the drive from the
supply and all other voltage sources.
WARNING!
The Safe torque off functionality is only achieved through the XSTO connector of
the inverter control unit (A41). True Safe torque off functionality is not achieved
through the XSTO connectors of other control units (such as the supply control
unit or the brake control unit).
The Safe torque off function is supported by any ACS880 inverter or drive control
program. It is not supported by supply, DC/DC converter or brake firmware.
WARNING!
The drive cannot detect or memorize any changes in the STO circuitry when the
drive control unit is not powered. If both STO circuits are closed and a level-type
start signal is active when the power is restored, it is possible that the drive starts
without a fresh start command. Take this into account in the risk assessment of
the system.
WARNING!
(With permanent magnet or synchronous reluctance [SynRM] motors only)
In case of a multiple IGBT power semiconductor failure, the drive can produce an
alignment torque which maximally rotates the motor shaft by 180/
p
degrees (with
permanent magnet motors) or 180/2
p
degrees (with synchronous reluctance
[SynRM] motors) regardless of the activation of the Safe torque off function.
p
denotes the number of pole pairs.
The Safe torque off function 93
Содержание ACS880-107LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 107LC inverter units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...10 ...
Страница 38: ...4 a 8 b 16 18 PE PE 10 38 Electrical installation ...
Страница 39: ...13 12 21 Electrical installation 39 11 ...
Страница 44: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 44 Electrical installation ...
Страница 48: ...48 ...
Страница 54: ...54 ...
Страница 72: ...72 ...
Страница 108: ...108 ...
Страница 115: ...Above Sides Front in mm in mm in mm 9 85 250 0 0 59 1500 Technical data 115 ...
Страница 124: ...124 ...
Страница 130: ...Inverter module cubicle with two R8i modules bottom cable exit 130 Dimensions ...
Страница 131: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 131 ...
Страница 132: ... Units with common motor terminal cubicle H359 Cubicle width 300 mm bottom cable exit 132 Dimensions ...
Страница 133: ...Cubicle width 300 mm top cable exit Dimensions 133 ...
Страница 134: ...Cubicle width 400 mm bottom cable exit 134 Dimensions ...
Страница 135: ...Cubicle width 400 mm top cable exit Dimensions 135 ...
Страница 136: ...Cubicle width 600 mm bottom cable exit 136 Dimensions ...
Страница 137: ...Cubicle width 600 mm top cable exit Dimensions 137 ...
Страница 138: ...138 ...