10. Cover or remove the cooling fan.
11. Deactivate the control IOs of the fan in parameters
206.20 … 206.23
.
12. Reinstall all shrouding removed earlier.
Note:
Do not reinstall the DC fuses or busbars but store them elsewhere until the module
can be reinstalled.
13. In case the inverter unit has a DC switch/disconnector with a charging circuit, locate the
BSFC-xx charging controller. On the controller, disable the channel of the removed
module by using the appropriate DIP switch.
14. Switch on the power to the drive.
15. Enter the number of inverter modules present into parameter
95.13 Reduced run mode
.
16. Reset all faults and start the drive.
17. If the Safe torque off (STO) function is in use, perform a validation test. See the
instructions in chapter
The Safe torque off function (page 83)
The maximum current is now automatically limited according to the new inverter configuration.
A mismatch between the number of detected modules (parameter
95.14
) and the value set
in
95.13
will generate a fault.
Returning the module
1. Install the module in reverse order. Use the following tightening torques:
• DC busbar assembly to upper insulators (2 × M8): 9 N·m (6.6 lbf·ft)
• DC busbar assembly to lower insulators (2 × M10): 18 N·m (13.3 lbf·ft)
• Fuses to DC busbars: 50 N·m (37 lbf·ft) (Bussmann), 46 N·m (34 lbf·ft)
(Mersen/Ferraz-Shawmut)
• Module to cabinet frame (4 × M8): 22 N·m (16 lbf·ft)
• DC busbar assembly to module DC input (2 × M12): 70 N·m (52 lbf·ft)
2. Remove the plugs from the coolant pipes and reconnect the pipes to the module. See
the module replacement instructions.
3. Restore the original wiring (STO and control unit power supply whenever needed).
4. Reinstall any removed fan(s). Reconnect the control and power supply wiring of the fan.
5. Set parameter
95.13
to 0 to disable the reduced run function.
6. Activate the control IOs of the fan in parameters
206.20 … 206.23
.
7. If the Safe torque off (STO) function is in use, perform an acceptance test. See the
instructions in chapter
The Safe torque off function (page 83)
Maintenance 65
Содержание ACS880-107LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 107LC inverter units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...10 ...
Страница 38: ...4 a 8 b 16 18 PE PE 10 38 Electrical installation ...
Страница 39: ...13 12 21 Electrical installation 39 11 ...
Страница 44: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 44 Electrical installation ...
Страница 48: ...48 ...
Страница 54: ...54 ...
Страница 72: ...72 ...
Страница 108: ...108 ...
Страница 115: ...Above Sides Front in mm in mm in mm 9 85 250 0 0 59 1500 Technical data 115 ...
Страница 124: ...124 ...
Страница 130: ...Inverter module cubicle with two R8i modules bottom cable exit 130 Dimensions ...
Страница 131: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 131 ...
Страница 132: ... Units with common motor terminal cubicle H359 Cubicle width 300 mm bottom cable exit 132 Dimensions ...
Страница 133: ...Cubicle width 300 mm top cable exit Dimensions 133 ...
Страница 134: ...Cubicle width 400 mm bottom cable exit 134 Dimensions ...
Страница 135: ...Cubicle width 400 mm top cable exit Dimensions 135 ...
Страница 136: ...Cubicle width 600 mm bottom cable exit 136 Dimensions ...
Страница 137: ...Cubicle width 600 mm top cable exit Dimensions 137 ...
Страница 138: ...138 ...