Maintenance
After the operation of the circuit is validated at start-up, the STO function shall be maintained
by periodic proof testing. In high demand mode of operation, the maximum proof test interval
is 20 years. In low demand mode of operation, the maximum proof test interval is 5 or 2
years; see section
. It is assumed that all dangerous failures of the
STO circuit are detected by the proof test. To perform the proof test, do the
.
Note:
See also the Recommendation of Use CNB/M/11.050 (published by the European
co-ordination of Notified Bodies) concerning dual-channel safety-related systems with
electromechanical outputs:
• When the safety integrity requirement for the safety function is SIL 3 or PL e (cat. 3 or
4), the proof test for the function must be performed at least every month.
• When the safety integrity requirement for the safety function is SIL 2 (HFT = 1) or PL d
(cat. 3), the proof test for the function must be performed at least every 12 months.
The STO function of the drive does not contain any electromechanical components.
In addition to proof testing, it is a good practice to check the operation of the function when
other maintenance procedures are carried out on the machinery.
Include the Safe torque off operation test described above in the routine maintenance
program of the machinery that the drive runs.
If any wiring or component change is needed after start up, or the parameters are restored,
do the test given in section
Validation test procedure (page 91)
.
Use only spare parts approved by ABB.
Record all maintenance and proof test activities in the machine logbook.
■
Competence
The maintenance and proof test activities of the safety function must be carried out by a
competent person with adequate expertise and knowledge of the safety function as well as
functional safety, as required by IEC 61508-1 clause 6.
The Safe torque off function 95
Содержание ACS880-107LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 107LC inverter units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...10 ...
Страница 38: ...4 a 8 b 16 18 PE PE 10 38 Electrical installation ...
Страница 39: ...13 12 21 Electrical installation 39 11 ...
Страница 44: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 44 Electrical installation ...
Страница 48: ...48 ...
Страница 54: ...54 ...
Страница 72: ...72 ...
Страница 108: ...108 ...
Страница 115: ...Above Sides Front in mm in mm in mm 9 85 250 0 0 59 1500 Technical data 115 ...
Страница 124: ...124 ...
Страница 130: ...Inverter module cubicle with two R8i modules bottom cable exit 130 Dimensions ...
Страница 131: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 131 ...
Страница 132: ... Units with common motor terminal cubicle H359 Cubicle width 300 mm bottom cable exit 132 Dimensions ...
Страница 133: ...Cubicle width 300 mm top cable exit Dimensions 133 ...
Страница 134: ...Cubicle width 400 mm bottom cable exit 134 Dimensions ...
Страница 135: ...Cubicle width 400 mm top cable exit Dimensions 135 ...
Страница 136: ...Cubicle width 600 mm bottom cable exit 136 Dimensions ...
Страница 137: ...Cubicle width 600 mm top cable exit Dimensions 137 ...
Страница 138: ...138 ...