Operation principle
1. The Safe torque off activates (the activation switch is opened, or safety relay contacts
open).
2. The STO inputs of the drive control unit de-energize.
3. The control unit cuts off the control voltage from the output IGBTs.
4. The control program generates an indication as defined by parameter
31.22
(see the
firmware manual of the drive).
The parameter selects which indications are given when one or both STO signals are
switched off or lost. The indications also depend on whether the drive is running or
stopped when this occurs.
Note:
This parameter does not affect the operation of the STO function itself. The STO
function will operate regardless of the setting of this parameter: a running drive will stop
upon removal of one or both STO signals, and will not start until both STO signals are
restored and all faults reset.
Note:
The loss of only one STO signal always generates a fault as it is interpreted as a
malfunction of STO hardware or wiring.
5. The motor coasts to a stop (if running). The drive cannot restart while the activation
switch or safety relay contacts are open. After the contacts close, a reset may be needed
(depending on the setting of parameter
31.22
). A new start command is required to start
the drive.
90 The Safe torque off function
Содержание ACS880-107LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 107LC inverter units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...10 ...
Страница 38: ...4 a 8 b 16 18 PE PE 10 38 Electrical installation ...
Страница 39: ...13 12 21 Electrical installation 39 11 ...
Страница 44: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 44 Electrical installation ...
Страница 48: ...48 ...
Страница 54: ...54 ...
Страница 72: ...72 ...
Страница 108: ...108 ...
Страница 115: ...Above Sides Front in mm in mm in mm 9 85 250 0 0 59 1500 Technical data 115 ...
Страница 124: ...124 ...
Страница 130: ...Inverter module cubicle with two R8i modules bottom cable exit 130 Dimensions ...
Страница 131: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 131 ...
Страница 132: ... Units with common motor terminal cubicle H359 Cubicle width 300 mm bottom cable exit 132 Dimensions ...
Страница 133: ...Cubicle width 300 mm top cable exit Dimensions 133 ...
Страница 134: ...Cubicle width 400 mm bottom cable exit 134 Dimensions ...
Страница 135: ...Cubicle width 400 mm top cable exit Dimensions 135 ...
Страница 136: ...Cubicle width 600 mm bottom cable exit 136 Dimensions ...
Страница 137: ...Cubicle width 600 mm top cable exit Dimensions 137 ...
Страница 138: ...138 ...