Maintenance and hardware diagnostics 121
Heatsink
The drive heatsink fins pick up dust from the cooling air. The drive runs into
overtemperature warnings and faults if the heatsink is not clean. When necessary,
clean the heatsink as follows.
WARNING!
Obey the instructions in chapter
on page
Ignoring the instructions can cause physical injury or death, or damage to the
equipment.
WARNING!
Use a vacuum cleaner with antistatic hose and nozzle. Using a
normal vacuum cleaner creates static discharges which can damage circuit
boards.
1. Stop the drive and disconnect it from the power line. Wait for 5 minutes and then
make sure by measuring that there is no voltage. See section
before you start the work.
2. Remove the cooling fan(s). See section
on page
.
3. Blow clean, dry and oil free compressed air from bottom to top and
simultaneously use a vacuum cleaner at the air outlet to trap the dust.
Note:
If there is a risk of dust entering adjoining equipment, perform the cleaning
in another room.
4. Reinstall the cooling fan(s).
R
Replacement
(R) Replacement
in harsh conditions*
O
Other work
(commissioning, tests, measurements, etc.)
* Ambient temperature constantly over 40 °C, especially dusty or humid ambient conditions,
cyclic heavy load, or continuous nominal (full) load.
To maintain the best possible performance and reliability of the drive, inspect the drive
annually. Contact the service at least once in three years for replacement of aging
components.
Note:
Recommended maintenance intervals and component replacements are based on
operation in specified ambient conditions.
Содержание ACS580-01 drives
Страница 1: ...ABB general purpose drives Hardware manual ACS580 01 drives 0 75 to 250 kW...
Страница 4: ......
Страница 11: ...Table of contents 11 Document library on the Internet 225...
Страница 12: ...12 Table of contents...
Страница 36: ...36 Operation principle and hardware description Locations of the labels on the drive 1 2 3 1 2 3...
Страница 72: ...72 Planning the electrical installation...
Страница 79: ...Electrical installation 79 R6 R9 3 3 4...
Страница 108: ...108 Electrical installation 0 5 0 6 N m 0 5 0 6 N m 10 4 3 R5 4 6 8 7 4 8 9 5 11 11 0 4 lbf ft 0 4 lbf ft...
Страница 109: ...Electrical installation 109 R6 R9 0 5 0 6 N m 0 4 lbf ft 0 5 0 6 N m 0 4 lbf ft M4 20 4 6 10 3 4 4 5 7 8 9 8 11 11...
Страница 123: ...Maintenance and hardware diagnostics 123 3 Install the fan assembly in reverse order 2b R0 R1 R2 2b R3 2b R4 2b...
Страница 132: ...132 Maintenance and hardware diagnostics...
Страница 168: ...168 Dimension drawings Frame R0 IP21 3AXD10000257110...
Страница 169: ...Dimension drawings 169 Frame R0 IP55 3AXD10000341562...
Страница 170: ...170 Dimension drawings Frame R1 IP21 3AXD10000257188...
Страница 171: ...Dimension drawings 171 Frame R1 IP55 3AXD10000336766...
Страница 172: ...172 Dimension drawings Frame R2 IP21 3AXD10000257203...
Страница 173: ...Dimension drawings 173 Frame R2 IP55 3AXD10000341578...
Страница 174: ...174 Dimension drawings Frame R3 IP21 3AXD10000257219...
Страница 175: ...Dimension drawings 175 Frame R3 IP55 3AXD10000335424...
Страница 176: ...176 Dimension drawings Frame R4 IP21 3AXD10000332430...
Страница 177: ...Dimension drawings 177 Frame R4 IP55 3AXD10000427933...
Страница 178: ...178 Dimension drawings Frame R5 IP21 3AXD10000412280...
Страница 179: ...Dimension drawings 179 Frame R5 IP55 3AXD10000415964...
Страница 180: ...180 Dimension drawings Frame R6 IP21 3AXD10000258705...
Страница 181: ...Dimension drawings 181 Frame R6 IP55 3AXD10000330667...
Страница 182: ...182 Dimension drawings Frame R7 IP21 3AXD10000258995...
Страница 183: ...Dimension drawings 183 Frame R7 IP55 3AXD10000330932...
Страница 184: ...184 Dimension drawings Frame R8 IP21 3AXD10000287670...
Страница 185: ...Dimension drawings 185 Frame R8 IP55 3AXD10000332446...
Страница 186: ...186 Dimension drawings Frame R9 IP21 3AXD10000287428...
Страница 187: ...Dimension drawings 187 Frame R9 IP55 3AXD10000334310...
Страница 188: ...188 Dimension drawings...
Страница 196: ...196 Resistor braking...
Страница 226: ...Contact us AXD50000018826 Rev D EN 2015 11 02 www abb com drives www abb com drivespartners 3AXD50000018826D...