64 Parameters
0160
DIGITAL INPUT
STATUS
Binary value.
Displays the status of the drive inputs, starting with the left hand side
digit = Digital Input 1 etc.
0183
DC BUS VOLTAGE
RIPPLE LEVEL
Displays the level of ripple present on the DC Bus Voltage in V DC.
This parameter is used by the drive for various internal protection and
monitoring functions.
0188
OPERATING TIME
ACCUMULATED
WITH HEATSINK
TEMPERATURE
ABOVE 85°C
Displays the amount of time in hours and minutes that the drive has
operated for during its lifetime with a heatsink temperature in excess
of 85°C. This parameter is used by the drive for various internal
protection and monitoring functions. (HH:MM:SS)
0189
OPERATING TIME
ACCUMULATED
WITH AMBIENT
TEMPERATURE
ABOVE 80°C
Displays the amount of time in hours and minutes that the DRIVE has
operated for during its lifetime with an ambient temperature in excess
of 80°C. This parameter is used by the DRIVE for various internal
protection and monitoring functions. (HH:MM:SS)
0190
DRIVE INTERNAL
COOLING FAN
TOTAL OPERATING
TIME
Displays the total operating time of the drive internal cooling fans. The
first value shown is the number of hours. Pressing the Up key will
display the minutes and seconds. This is used for scheduled
maintenance information (HH:MM:SS)
0192
DC BUS VOLTAGE
RIPPLE LOG (22ms)
(V DC)
8 most recent values prior to trip, updated every 22ms.
0193
HEATSINK
TEMPERATURE LOG
(30s) (°C)
8 most recent values prior to trip, updated every 30s.
0194
AMBIENT
TEMPERATURE LOG
(30s) (°C)
8 most recent values prior to trip, updated every 30s.
04 FAULT HISTORY
Fault history (read-only)
0402
RUN TIME SINCE
LAST TRIP (1)
Run-time clock stopped by drive disable (or trip), reset on next enable
only if a trip occurred. Reset also on next enable after a drive power
down. (0 to 99 999 hours)
0406
DC BUS VOLTAGE
LOG
8 most recent values prior to trip, updated every 250ms. (0 … 1000V)
0415
RUN TIME SINCE
LAST TRIP (2)
Run-time clock stopped by drive disable (or trip), reset on next enable
only if a trip occurred (under-volts not considered a trip) – not reset
by power down / power up cycling unless a trip occurred prior to
power down.( 0 to 99 999 hours)
0416
RUN TIME SINCE
LAST DISABLE
Run-time clock stopped on drive disable, value reset on next enable.
(0 to 99 999 hours)
0417
DRIVE EFFECTIVE
SWITCHING
FREQUENCY
Actual drive effective output switching frequency. This value maybe
lower than the selected frequency in parameter
2606
EFFECTIVE
SWITCHING FREQUENCY if the drive is too hot. The drive will
automatically reduce the switching frequency to prevent an over
temperature trip and maintain operation. (4 to 32 kHz)
33 INFORMATION
Firmware package version, serial number etc..
ACS260-04.book Page 64 Thursday, December 24, 2020 4:33 PM
Содержание ACS260-04 Series
Страница 2: ...ACS260 04 book Page 2 Thursday December 24 2020 4 33 PM ...
Страница 4: ...ACS260 04 book Page 4 Thursday December 24 2020 4 33 PM ...
Страница 8: ...8 Table of contents ACS260 04 book Page 8 Thursday December 24 2020 4 33 PM ...
Страница 14: ...14 Safety ACS260 04 book Page 14 Thursday December 24 2020 4 33 PM ...
Страница 22: ...22 Mechanical installation ACS260 04 book Page 22 Thursday December 24 2020 4 33 PM ...
Страница 32: ...32 Electrical installation ACS260 04 book Page 32 Thursday December 24 2020 4 33 PM ...
Страница 92: ...92 Technical Data ACS260 04 book Page 92 Thursday December 24 2020 4 33 PM ...
Страница 96: ...96 Options and Kits ACS260 04 book Page 96 Thursday December 24 2020 4 33 PM ...