44 Application Macros
Note:
By default the PI reference is set for a digital reference level set in Parameter
4011 PI DIGITAL REFERENCE (SETPOINT).
When using an Analog reference set Parameter 4010 PI DIGITAL REFERENCE
(SETPOINT)= 1 (analog) and connect reference signal to analog input 1 (T6).
The default settings for proportional gain (parameter 4001), integral gain (Parameter
4002) and feedback mode (Parameter 4005) are suitable for most fan and pump
applications.
The analog reference used for PI controller can also be used as the local speed
reference when parameter 9902 DIGITAL INPUTS FUNCTION SELECT =1.
+24 Volt
Run (Enable)
PI / Preset Speed 1
External Trip
PI Feedback
0 Volt
Remote closed loop PI feedback control with Local
Preset speed 1 and motor thermistor trip
ACS260-04.book Page 44 Thursday, December 24, 2020 4:33 PM
Содержание ACS260-04 Series
Страница 2: ...ACS260 04 book Page 2 Thursday December 24 2020 4 33 PM ...
Страница 4: ...ACS260 04 book Page 4 Thursday December 24 2020 4 33 PM ...
Страница 8: ...8 Table of contents ACS260 04 book Page 8 Thursday December 24 2020 4 33 PM ...
Страница 14: ...14 Safety ACS260 04 book Page 14 Thursday December 24 2020 4 33 PM ...
Страница 22: ...22 Mechanical installation ACS260 04 book Page 22 Thursday December 24 2020 4 33 PM ...
Страница 32: ...32 Electrical installation ACS260 04 book Page 32 Thursday December 24 2020 4 33 PM ...
Страница 92: ...92 Technical Data ACS260 04 book Page 92 Thursday December 24 2020 4 33 PM ...
Страница 96: ...96 Options and Kits ACS260 04 book Page 96 Thursday December 24 2020 4 33 PM ...