Parameters 51
21 STOPPING
MODE/MAINS LOSS
RESPONSE
Stop mode of the motor
2102
STOP MODE
Selects the motor stop function
0 = Ramp to
stop
22 ACCEL/DECEL
Acceleration and deceleration times
2202
ACCELERATION
RAMP TIME
Acceleration ramp time from 0 to base speed (Parameter
9907
MOTOR RATED FREQUENCY) in seconds.
15.0 s
0.00…600.0 s
Time
2203
DECELERATION
RAMP TIME
Deceleration ramp time from base speed (Parameter
9907
MOTOR RATED FREQUENCY) to standstill in
seconds. When set to zero, fastest possible ramp time
without trip is activated.
15.0 s
0.00…600.0 s
Time
Setting
On Disable
On Mains loss
0
Ramp to Stop
(
2203
DECEL
RAMP TIME)
Ride Through (Recover
energy from load to
maintain operation)
1
Coast
Coast
2
Ramp to Stop
(
2203
DECEL
RAMP TIME)
Fast Ramp to Stop
(
2206
2
nd
DECEL
RAMP TIME), coast if
2206
is zero.
3
Ramp to Stop
(
2203
DECEL
RAMP TIME)
with AC flux
braking
Fast Ramp to Stop
(
2206
2
nd
DECEL
RAMP TIME), coast if
2206
is zero.
ACS260-04.book Page 51 Thursday, December 24, 2020 4:33 PM
Содержание ACS260-04 Series
Страница 2: ...ACS260 04 book Page 2 Thursday December 24 2020 4 33 PM ...
Страница 4: ...ACS260 04 book Page 4 Thursday December 24 2020 4 33 PM ...
Страница 8: ...8 Table of contents ACS260 04 book Page 8 Thursday December 24 2020 4 33 PM ...
Страница 14: ...14 Safety ACS260 04 book Page 14 Thursday December 24 2020 4 33 PM ...
Страница 22: ...22 Mechanical installation ACS260 04 book Page 22 Thursday December 24 2020 4 33 PM ...
Страница 32: ...32 Electrical installation ACS260 04 book Page 32 Thursday December 24 2020 4 33 PM ...
Страница 92: ...92 Technical Data ACS260 04 book Page 92 Thursday December 24 2020 4 33 PM ...
Страница 96: ...96 Options and Kits ACS260 04 book Page 96 Thursday December 24 2020 4 33 PM ...