98
ACS 160 User’s Manual
Group 54: Braking (Electromechanical Brake Control)
The versatile braking features of the ACS 160 include capability to control electromechanical brake.
Electromechanical brake can be controlled by using programmable relay outputs of the ACS 160.
The brake is applied when the motor is in stop (the relay output is de-energised).
Electromechanical brake control is enabled by first setting parameter 1401
RELAY
OUTPUT
1 (or 1402
RELAY
OUTPUT
2) to value 32 (
MEC
BR
CNTRL
). Parameters 5401
MBRK
OPEN
DLY
and 5403
MBRK
FREQ
LVL
are used to adjust the operation of the mechanical brake. Refer to Figure 28.
Note!
Observe the relay output ratings as given in Reference Section
When necessary, use an
additional contactor to supply the brake coil.
Code Description
5401
MBRK OPEN DLY
Release delay for external brake. This delay specifies the time which passes from the brake open command
to the moment when the brake is mechanically open.
Note!
Value of this parameter should be slightly longer than the actual time it takes for the external brake to
release. Too large of a value may lead to overcurrent tripping as the motor shaft can not rotate due to
operation of the brake.
5403
MBRK FREQ LVL
The level of output frequency below which the external brake is applied. This frequency level should be low
enough that the speed of the motor is reduced almost to zero during the closing delay of the external brake.
Содержание ACS 160
Страница 2: ......
Страница 4: ......
Страница 10: ...viii ACS 160 User s Manual ...
Страница 12: ...2 ACS 160 User s Manual ...
Страница 32: ...22 ACS 160 User s Manual ...
Страница 42: ...32 ACS 160 User s Manual ...
Страница 56: ...46 ACS 160 User s Manual ...
Страница 116: ...106 ACS 160 User s Manual ...
Страница 122: ...112 ACS 160 User s Manual ...
Страница 126: ...116 ACS 160 User s Manual ...
Страница 136: ...126 ACS 160 User s Manual ...
Страница 137: ......