6
ACS 160 User’s Manual
Reference Sections
A Environment for Storage, Transportation and Stationary Use
ACS 160
Stationary Use
Storage and Transportation
in the protective package
Installation Site Altitude
• 0…1000 m (0...3300 ft) if P
N
and
I
2
100%
• 1000…2000 m (3300...6600 ft)
if P
N
and
I
2
derated 1% every
100 m (330 ft) above 1000 m
(3300 ft)
-
Ambient Temperature
• -10…40
°
C (14...104
°
F) in
motor mounting
• 0...40
°
C (32...104
°
F) in wall
mounting
• max. 50
°
C (122
°
F) with
-40...+70
°
C (-40...+158
°
F)
Contamination Levels
(IEC 721-3-3)
According to IP65 classification
• chemical gases: Class 3C3
• solid particles: Class 3S3
Storage
• chemical gases: Class 1C2
• solid particles: Class 1S3
Transportation
• chemical gases: Class 2C2
• solid particles: Class 2S2
Sinusoidal Vibration
(IEC-721-3-3, 2
nd
edition
1994-12)
In motor mounting:
• 2-9 Hz max amplitude 3 mm
(0.118 in)
• 9-200 Hz max acceleration
10 m/s
2
(33 ft/s
2
)
In wall mounting:
• 2-9 Hz max amplitude 1.5 mm
(0.06 in)
• 9-200 Hz max acceleration
5 m/s
2
(16 ft/s
2
)
Shock
(IEC-721-3-3, 2
nd
edition
1994-12)
In motor mounting:
• max 250 m/s
2
(820 ft/s
2
), 6 ms
In wall mounting:
• max 70 m/s
2
(230 ft/s
2
), 11 ms
• max. 300 m/s
2
(985 ft/s
2
), 18 ms
Free Fall
not allowed
• 76 cm (30 in.), according to ISTA 1A
Содержание ACS 160
Страница 2: ......
Страница 4: ......
Страница 10: ...viii ACS 160 User s Manual ...
Страница 12: ...2 ACS 160 User s Manual ...
Страница 32: ...22 ACS 160 User s Manual ...
Страница 42: ...32 ACS 160 User s Manual ...
Страница 56: ...46 ACS 160 User s Manual ...
Страница 116: ...106 ACS 160 User s Manual ...
Страница 122: ...112 ACS 160 User s Manual ...
Страница 126: ...116 ACS 160 User s Manual ...
Страница 136: ...126 ACS 160 User s Manual ...
Страница 137: ......