ACS 160 User’s Manual
67
21 =
ACS
OVERLOAD
Relay is energised when ACS 160 overload alarm or fault exists.
22 =
UNDERVOLTAGE
Relay is energised when undervoltage alarm or fault exists.
23 = AI1
LOSS
Relay is energised when AI1 signal is lost.
24 = AI2
LOSS
Relays energised when AI2 signal is lost.
25 =
MOT
OVR
TEMP
Relay is energised when motor overtemperature alarm or fault exists.
26 =
STALL
Relay is energised when stall alarm or fault exists.
27 =
UNDERLOAD
Relay is energised when underload alarm or fault exists.
28 =
PID
SLEEP
Relay is energised when PID sleep function is active.
29 - 30 = (reserved)
31 =
STARTED
Relay is energised when drive receives start command (even if Run Enable signal is not present). Relay is
de-energised when stop command is received or fault occurs.
32 =
MEC
BR
CNTRL
Relay is used to control electromechanical brake. Refer to Group 54: Braking for more information.
33 =
BCH
FAULT
Relay is de-energised if brake resistor is overloaded. Refer to brake resistor instructions for more
information.
34 =
AT
TARGET
Target positioning is reached. Use only when positioning macro is used.
1402
RELAY OUTPUT 2
Relay output 2 content. Refer to parameter 1401
RELAY
OUTPUT
1.
1403
RO 1 ON DELAY
Switch-on delay for relay 1.
Figure 8
1404
RO 1 OFF DELAY
Switch-off delay for relay 1
1405
RO 2 ON DELAY
Switch-on delay for relay 2.
1406
RO 2 OFF DELAY
Switch-off delay for relay 2.
Code Description
1403
ON
DELAY
1404
OFF
DELAY
Selected controlling signal
Relay status
Содержание ACS 160
Страница 2: ......
Страница 4: ......
Страница 10: ...viii ACS 160 User s Manual ...
Страница 12: ...2 ACS 160 User s Manual ...
Страница 32: ...22 ACS 160 User s Manual ...
Страница 42: ...32 ACS 160 User s Manual ...
Страница 56: ...46 ACS 160 User s Manual ...
Страница 116: ...106 ACS 160 User s Manual ...
Страница 122: ...112 ACS 160 User s Manual ...
Страница 126: ...116 ACS 160 User s Manual ...
Страница 136: ...126 ACS 160 User s Manual ...
Страница 137: ......