84 Electrical installation
WARNING!
As the inputs pictured above are not insulated according to IEC
60664, the connection of the motor temperature sensor requires double or
reinforced insulation between motor live parts and the sensor. If the assembly
does not fulfil the requirement,
•
the I/O board terminals must be protected against contact and must not be connected
to other equipment
or
•
the temperature sensor must be isolated from the I/O terminals.
Start interlock (XDI:A)
Terminal XDI:A must be jumpered to XD24:3 to enable the drive start.
Drive-to-drive link (XD2D)
The drive-to-drive link is a daisy-chained RS-485 transmission line that allows basic
master/follower communication with one master drive and multiple followers.
Termination activation jumper T (see section
above) next to this terminal block
must be set to the ON position on the drives at the ends of the drive-to-drive link. On
intermediate drives, the jumper must be set to the OFF position.
Shielded twisted-pair cable (~100 ohm, for example PROFIBUS-compatible cable) must
be used for the wiring. For best immunity, high quality cable is recommended. The cable
should be kept as short as possible; the maximum length of the link is 50 meters (164 ft).
Unnecessary loops and running the cable near power cables (such as motor cables) must
be avoided. The cable shields must to be grounded to the control cable clamp plate on the
drive as shown on page
.
The following diagram shows the wiring of the drive-to-drive link.
XD2D
...
1
T
J3
Termination
ON
JCU
Drive 1
B
2
A
3
BG
N
D
XD2D
1
J3
Termination
OFF
JCU
Drive 2
B
2
A
3
BG
N
D
T
XD2D
1
T
J3
Termination
ON
JCU
Drive n
B
2
A
3
BG
N
D
Содержание ACQ810
Страница 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Страница 4: ......
Страница 16: ...16 Safety instructions...
Страница 30: ...30 Operation principle and hardware description...
Страница 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Страница 70: ...70 Planning the electrical installation...
Страница 88: ...88 Electrical installation...
Страница 94: ...94 Start up...
Страница 96: ...96 Fault tracing...
Страница 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Страница 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Страница 124: ...124 Dimension drawings Drive control unit JCU Can be mounted on a DIN rail EN 50022 35 mm x 7 5 mm...
Страница 125: ...Dimension drawings 125 Package...
Страница 127: ...Dimension drawings 127 Frame with busbars on the left side inches 68440513_5 6 A 64801082 asm E...
Страница 128: ...128 Dimension drawings...
Страница 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...