52 Planning the electrical installation
European Union
To meet the European Union Directives, according to standard EN 60204-1,
Safety of
Machinery
, the disconnecting device must be one of the following types:
•
switch-disconnector of utilization category AC-23B (EN 60947-3)
•
disconnector that has an auxiliary contact that in all cases causes switching devices to
break the load circuit before the opening of the main contacts of the disconnector
(EN 60947-3)
•
circuit breaker suitable for isolation in accordance with EN 60947-2.
Other regions
The disconnecting device must conform to the applicable safety regulations.
Selecting and dimensioning the main contactor
If a main contactor is used, its utilization category (number of operations under load) must
be AC-1 according to IEC 60947-4,
Low-voltage switchgear and controlgear
. Dimension
the main contactor according to the nominal voltage and current of the drive.
Protecting the motor insulation and bearings
The drive employs modern IGBT inverter technology. Regardless of frequency, the drive
output comprises pulses of approximately the drive DC bus voltage with a very short rise
time. The pulse voltage can almost double at the motor terminals, depending on the
attenuation and reflection properties of the motor cable and the terminals. This can cause
additional stress on the motor and motor cable insulation.
Modern variable speed drives with their fast rising voltage pulses and high switching
frequencies can generate current pulses that flow through the motor bearings, which can
gradually erode the bearing races and rolling elements.
Optional du/dt filters protect motor insulation system and reduce bearing currents.
Common mode filters mainly reduce bearing currents. insulated N-end (non-drive end)
bearings protect the motor bearings. See section
Checking the compatibility of the motor
below for the required filters and N-end bearings to be used with the drive.
Select and install the cables according to the instructions given in this manual.
Checking the compatibility of the motor and drive
Use an AC induction motor with the drive. Several induction motors can be connected to
the drive at a time.
Select the motor and drive according to the rating tables in chapter
1. Check that the motor ratings lie within the allowed ranges of the drive control program:
2. motor nominal voltage is in the range of 1/2 ... 2 ·
U
N
3. motor nominal current is 1/3 ... 1 ·
I
max
of the drive in DTC control and
0 ... 1 ·
I
max
in scalar control. The control mode is selected by a drive parameter.
4. Consult the motor manufacturer before using a motor in a drive system where the
motor nominal voltage differs from the AC power source voltage.
Содержание ACQ810
Страница 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Страница 4: ......
Страница 16: ...16 Safety instructions...
Страница 30: ...30 Operation principle and hardware description...
Страница 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Страница 70: ...70 Planning the electrical installation...
Страница 88: ...88 Electrical installation...
Страница 94: ...94 Start up...
Страница 96: ...96 Fault tracing...
Страница 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Страница 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Страница 124: ...124 Dimension drawings Drive control unit JCU Can be mounted on a DIN rail EN 50022 35 mm x 7 5 mm...
Страница 125: ...Dimension drawings 125 Package...
Страница 127: ...Dimension drawings 127 Frame with busbars on the left side inches 68440513_5 6 A 64801082 asm E...
Страница 128: ...128 Dimension drawings...
Страница 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...