66 Planning the electrical installation
Alternative 2: When you have selected to use the default motor control mode (DTC) and
motor ramp stop in the drive, open the contactor as follows:
1. Give a stop command to the drive.
2. Wait until the drive decelerates the motor to zero speed.
3. Open the contactor.
Alternative 3: When you have selected to use the scalar motor control mode in the drive,
open the contactor as follows:
1. Give a stop command to the drive.
2. Open the contactor.
WARNING!
When you have the default motor control mode (DTC) in use, never
open the output contactor while the drive rotates the motor. The DTC motor
control operates extremely fast, much faster than it takes for the contactor to open
its contacts. When the contactor starts opening while the drive rotates the motor, the DTC
will try to maintain the load current by immediately increasing the drive output voltage to
the maximum. This will damage, or even burn the contactor completely.
Implementing a bypass connection
If bypassing is required, employ mechanically or electrically interlocked contactors
between the motor and the drive and between the motor and the power line. Ensure with
the interlocking that the contactors cannot be closed simultaneously.
Follow this control sequence:
1. Stop the drive.
2. Stop the motor.
3. Open the contactor between the drive and the motor.
4. Close the contactor between the motor and the power line.
Содержание ACQ810
Страница 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Страница 4: ......
Страница 16: ...16 Safety instructions...
Страница 30: ...30 Operation principle and hardware description...
Страница 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Страница 70: ...70 Planning the electrical installation...
Страница 88: ...88 Electrical installation...
Страница 94: ...94 Start up...
Страница 96: ...96 Fault tracing...
Страница 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Страница 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Страница 124: ...124 Dimension drawings Drive control unit JCU Can be mounted on a DIN rail EN 50022 35 mm x 7 5 mm...
Страница 125: ...Dimension drawings 125 Package...
Страница 127: ...Dimension drawings 127 Frame with busbars on the left side inches 68440513_5 6 A 64801082 asm E...
Страница 128: ...128 Dimension drawings...
Страница 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...