![ABB ACQ810 Скачать руководство пользователя страница 113](http://html1.mh-extra.com/html/abb/acq810/acq810_hardware-manual_3423066113.webp)
Technical data 113
Terminal and lead-through data for the power cables
Input, motor and DC cable terminal sizes (per phase), maximum accepted cable and
tightening torques are given below.
Two-hole 1/2 inch diameter cable lugs can be used.
Terminal data for the control cables
U1, V1, W1, U2, V2, W2, UDC+, UDC-
Grounding PE
Number of holes
per phase
Max. cable
Screw
Tightening
torque
Screw
Tightening
torque
mm
2
N·m
N·m
3 3×240
M12
50...75
M10
30...44
Max. cable
U1, V1, W1, U2, V2, W2, UDC+, UDC-
Grounding PE
Screw
Tightening torque
Screw
Tightening torque
kcmil/AWG
lbf·ft
lbf·ft
3 × 700 MCM
1/2
37...55
3/8
22...32
Electrical power network specification
Voltage (
U
1
)
380 … 480 V AC 3-phase
± 10%
Rated conditional short-
circuit current (IEC 60439-1)
65 kA when protected by fuses given in the fuse tables
Short-circuit current
protection (UL 508C,
CSA C22.2 No. 14-05)
US and Canada: The drive is suitable for use on a circuit capable of
delivering not more than 100 kA symmetrical amperes (rms) at 500 V
maximum when protected by fuses given in table
.
Frequency
48 to 63 Hz, maximum rate of change 17%/s
Imbalance
Max.
± 3% of nominal phase to phase input voltage
Fundamental power factor
(cos phi
1
)
0.98 (at nominal load)
Motor connection data
Motor types
Asynchronous AC induction motors
Voltage (
U
2
)
0 to
U
1
,
3-phase symmetrical, U
max
at the field weakening point
Frequency
0…500 Hz
Current
Switching frequency
3 kHz (typically)
Maximum recommended
motor cable length
300 m (984 ft).
Note:
With motor cables longer than 100 m (328 ft) the EMC Directive
requirements may not be fulfilled.
Содержание ACQ810
Страница 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Страница 4: ......
Страница 16: ...16 Safety instructions...
Страница 30: ...30 Operation principle and hardware description...
Страница 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Страница 70: ...70 Planning the electrical installation...
Страница 88: ...88 Electrical installation...
Страница 94: ...94 Start up...
Страница 96: ...96 Fault tracing...
Страница 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Страница 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Страница 124: ...124 Dimension drawings Drive control unit JCU Can be mounted on a DIN rail EN 50022 35 mm x 7 5 mm...
Страница 125: ...Dimension drawings 125 Package...
Страница 127: ...Dimension drawings 127 Frame with busbars on the left side inches 68440513_5 6 A 64801082 asm E...
Страница 128: ...128 Dimension drawings...
Страница 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...