60 Planning the electrical installation
Relay cable type
The cable type with braided metallic screen (for example ÖLFLEX by LAPPKABEL,
Germany) has been tested and approved by ABB.
Control panel cable length and type
In remote use, the cable connecting the control panel to the drive must not exceed 3
meters (10 ft). The cable type tested and approved by ABB is used in control panel option
kits.
Routing the cables
Route the motor cable away from other cable routes. Motor cables of several drives can be
run in parallel installed next to each other. It is recommended that the motor cable, input
power cable and control cables be installed on separate trays. Avoid long parallel runs of
motor cables with other cables in order to decrease electromagnetic interference caused
by the rapid changes in the drive output voltage.
Where control cables must cross power cables ensure they are arranged at an angle as
near to 90 degrees as possible. Do not run extra cables through the drive.
The cable trays must have good electrical bonding to each other and to the grounding
electrodes. Aluminium tray systems can be used to improve local equalizing of potential.
A diagram of the cable routing is shown below.
90 °
min 500 mm (20 in.)
Motor cable
Input power cable
Control cables
min 200 mm (8 in.)
min 300 mm (12 in.)
Motor cable
Power cable
Drive
Содержание ACQ810
Страница 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Страница 4: ......
Страница 16: ...16 Safety instructions...
Страница 30: ...30 Operation principle and hardware description...
Страница 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Страница 70: ...70 Planning the electrical installation...
Страница 88: ...88 Electrical installation...
Страница 94: ...94 Start up...
Страница 96: ...96 Fault tracing...
Страница 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Страница 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Страница 124: ...124 Dimension drawings Drive control unit JCU Can be mounted on a DIN rail EN 50022 35 mm x 7 5 mm...
Страница 125: ...Dimension drawings 125 Package...
Страница 127: ...Dimension drawings 127 Frame with busbars on the left side inches 68440513_5 6 A 64801082 asm E...
Страница 128: ...128 Dimension drawings...
Страница 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...