322
Parameter listing and descriptions
ACH550-01 User's Manual
5 =
DI
5 – Enables the Interlock function, and assigns a digital input
(starting with
DI
5) to the interlock signal for each PFA relay. These
assignments are defined in the following table and depend on:
• the number of PFA relays [number of parameters 1401…1403 and
1410…1412 with value = 31 (PFA)]
• the Autochange function status (disabled if 8118
AUTOCHNG
INTERV
=
0.0, and otherwise enabled).
6 =
DI
6 – Enables the Interlock function, and assigns digital input
DI
6 to
the interlock signal for the speed regulated motor.
• Requires 8118
AUTOCHNG
INTERV
= 0.0.
Code Description
Range
No. PFA
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI
1…
DI
4: Free
DI
5: Speed Reg Motor
DI
6: Free
Not allowed
1
DI
1…
DI
4: Free
DI
5: Speed Reg Motor
DI
6: First PFA Relay
DI
1…
DI
4: Free
DI
5: First PFA Relay
DI
6: Free
2
Not allowed
DI
1…
DI
4: Free
DI
5: First PFA Relay
DI
6: Second PFA Relay
3…6
Not allowed
Not allowed
No. PFA
relays
Autochange disabled
Autochange enabled
0
DI
1…
DI
5: Free
DI
6: Speed Reg Motor
Not allowed
1
Not allowed
DI
1…
DI
5: Free
DI
6: First PFA Relay
2…6
Not allowed
Not allowed
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com