Parameter listing and descriptions
235
ACH550-01 User's Manual
2305
AUTOTUNE RUN
0=OFF, 1=ON
Starts automatic tuning of the speed controller.
0 =
OFF
– Disables the Autotune creation process. (Does not disable the
operation of Autotune settings.)
1 =
ON
– Activates speed controller autotuning. Automatically reverts to
OFF
.
Procedure:
Note:
The motor load must be connected.
• Run the motor at a constant speed of 20 to 40% of the rated speed.
• Change the autotuning parameter 2305 to
ON
.
The drive:
• Accelerates the motor.
• Calculates values for proportional gain and integration time.
• Changes parameters 2301 and 2302 to these values.
• Resets 2305 to
OFF
.
Code Description
Range