Parameter listing and descriptions
201
ACH550-01 User's Manual
Group 14: RELAY OUTPUTS
This group defines the condition that activates each of the relay
outputs.
Code Description
Range
1401
RELAY OUTPUT 1
0…47
Defines the event or condition that activates relay 1 – what relay output
1 means.
0 =
NOT
SEL
– Relay is not used and is de-energised.
1 =
READY
– Energise the relay when the drive is ready to function.
Requires:
• Run enable signal is present.
• No faults exist.
• Supply voltage is within range.
• Emergency Stop command is not on.
2 =
RUN
– Energise the relay when the drive is running.
3 =
FAULT
(-1) – Energise the relay when power is applied. De-energise
when a fault occurs.
4 =
FAULT
– Energise the relay when a fault is active.
5 =
ALARM
– Energise the relay when an alarm is active.
6 =
REVERSED
– Energise the relay when the motor rotates in reverse
direction.
7 =
STARTED
– Energise the relay when the drive receives a start
command (even if Run enable signal is not present). De-energise the
relay when the drive receives a stop command or a fault occurs.
8=
SUPRV
1
OVER
– Energise the relay when the first supervised
parameter (3201) exceeds the limit (3203).
• See
Group 32: SUPERVISION
.
9 =
SUPRV
1
UNDER
– Energise the relay when the first supervised
parameter (3201) drops below the limit (3202).
• See
Group 32: SUPERVISION
.
10 =
SUPRV
2
OVER
– Energise the relay when the second supervised
parameter (3204) exceeds the limit (3206).
• See
Group 32: SUPERVISION
.
11 =
SUPRV
2
UNDER
– Energise the relay when the second supervised
parameter (3204) drops below the limit (3205).
• See
Group 32: SUPERVISION
.
12 =
SUPRV
3
OVER
– Energise the relay when the third supervised
parameter (3207) exceeds the limit (3209).
• See
Group 32: SUPERVISION
.
13 =
SUPRV
3
UNDER
– Energise the relay when the third supervised
parameter (3207) drops below the limit (3208).
• See
Group 32: SUPERVISION
.