176
Parameter listing and descriptions
ACH550-01 User's Manual
0145
MOTOR TEMP
-10…200 °C /
0…5000 ohm
Motor temperature in degrees Celsius / PTC resistance in ohms.
• Applies only if motor temperature sensor is set up. See parameter
3501.
0150
CB TEMP
-20.0…150.0 °C
Temperature of the drive control board in degrees Celsius.
Note:
Some drives have a control board (OMIO) that does not support
this feature. These drives always show the constant value of 25.0 °C.
0153
MOT THERM STRESS
0.0…100.0%
Estimated rise of the motor temperature. Value equals to the estimated
motor thermal stress as a percentage of the motor temperature trip
level.
0158
PID COMM VALUE 1
-32768…+32767
Data received from fieldbus for PID control (PID1 and PID2)
.
0159
PID COMM VALUE 2
-32768…+32767
Data received from fieldbus for PID control (PID1 and PID2)
.
0174
SAVED KWH
0.0…999.9 kWh
Energy saved in kWh compared to the energy used when the load is
connected directly to the supply. See the note on page
293
.
• The counter value is accumulated till it reaches 999.9 after which the
counter rolls over and starts again from 0.0 and the counter value of
signal 0175 is incremented by one.
• Can be reset with parameter 4509
ENERGY
RESET
(resets all energy
calculators at the same time).
• See
Group 45: ENERGY SAVING
.
0175
SAVED MWH
0…65535 MWh
Energy saved in MWh compared to the energy used when the load is
connected directly to the supply. See the note on page
293
.
• The counter value is accumulated till it reaches 65535 after which the
counter rolls over and starts again from 0.
• Can be reset with parameter 4509
ENERGY
RESET
(resets all energy
calculators at the same time).
• See
Group 45: ENERGY SAVING
.
Code Description
Range
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com